Final | 8/15/2019 | 8/16/2019 | 8/16/2019 | A | PASS |
James Ady
|
|
|
HO on site, thank you!! Phone #: ###-#### Inspection requested via web by Darryn Coburn Corrections made final ok
|
Final | 8/14/2019 | 8/15/2019 | 8/15/2019 | A | FAIL |
Rock A. Hudson
|
|
|
HO on site Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.12(A)- Unused openings shall be closed by approved means. KO seal in bottom of panel, Connector needed on grounding electrode conductor at exterior disconnect. 300.4(G)- Insulating bushings shall be installed where #4 or larger enter an enclosure.
|
Rough-In Permanent Service | 7/18/2019 | 7/19/2019 | 7/19/2019 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 223.31 Shall disc all ungrounded conductors when passing through a detached structure. Will allow cover as long as by final disc is mounted on exterior of garage and concrete encased electrode is re-routed to disc. U/G from house to garage ok to cover and garage ok to cover as well....
|
Issue PAID IN FULL permit | | | 7/8/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/8/2019 | | DONE |
|
|
|
This permit was created on the web by Darryn Coburn
|