Final | 11/5/2019 | 11/6/2019 | 11/6/2019 | P | PASS |
Mark Moncarr
|
|
|
Corbin Metcalf ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Ok final.
|
Electrical Rough-In | 7/25/2019 | 7/26/2019 | 7/26/2019 | P | PASS |
Mark Moncarr
|
|
|
Corbin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Ok cover above garage. Talked to Corbin about installing a couple of outlets on back of half wall.
|
Electrical Rough-In | 7/15/2019 | 7/16/2019 | 7/16/2019 | A | NR |
Rock A. Hudson
|
|
|
Rough in inspection and consult with a few questions regarding job. Corbin Metcalf ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Rough in not ready Discussed removing subfeed from house to garage due to equipment ground must be added and small conduit between. Metal underground water pipe from house to garage must be added to grounding electrode system. Up bath does not have a basin in stool room so dedicated circuit not required. If clothes rod present in closet then AFCI protection required upstairs. Contractor believes he will pull sub feed to panel in garage from service mounted on garage eliminating most code issues.
|
Issue PAID IN FULL permit | | | 7/15/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/15/2019 | | DONE |
|
|
|
This permit was created on the web by Samatha Solberg
|