Temporary Service | 7/18/2019 | 7/19/2019 | 7/19/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson t/s u/g n ok
|
Temporary Service | 7/17/2019 | 7/18/2019 | 7/18/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson 110.3- 250 GFCI not installed as per instructions. 110.14(D)- Connections shall be torqued to spec. Ground rod acorn clamp loose.
|
Issue PAID IN FULL permit | | | 7/16/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/16/2019 | | DONE |
|
|
|
This permit was created on the web by David Nelson
|