Conference | 7/16/2019 | 7/17/2019 | 7/17/2019 | A | DONE |
Eric Story
|
|
|
Please call me half hour before so I can get electrician to meet you there. Thank You Dawn ###-#### Phone #: ###-#### Inspection requested via web by Kendra Lanham Discuss burned service lugs, will either replace with like for like to avoid complete change out, also talked about adding a gutter under existing meter pack to tap to another meter main to refeed unit and all grounding at this point will be brought up to current code as required....
|
Issue PAID IN FULL permit | | | 7/16/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/16/2019 | | DONE |
|
|
|
This permit was created on the web by Kendra Lanham
|