First Notice | 10/31/2019 | 10/31/2019 | 2/17/2020 | | DONE |
James Ady
|
|
|
This permit finaled on the web by Tom Jenkins
|
Final | 10/31/2019 | 10/31/2019 | 10/31/2019 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Tom Jenkins final ok
|
Final | 10/25/2019 | 10/28/2019 | 10/28/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Tom Jenkins Corrections not complete. Unable to final due to plan modification is under review. 210.8(B)- All 120 volt 15 and 20 amp receptacle outlets located with in 6' of a sink shall have GFCI protection. Dishwasher, refrigerator. Called and had ELE attached to BLD19-02257.
|
Final | 10/23/2019 | 10/23/2019 | 10/23/2019 | P | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Tom Jenkins 210.8 receps within 6ft of sink shall be GFCI protected. (Janitor closet) 210.62 Show room receps required. (Marked on print to stay) 422.30 Disc. shall be readily accessible ( Water heater disc is located on ceiling)
|
Electrical Rough-In | 9/17/2019 | 9/17/2019 | 9/17/2019 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Tom Jenkins Walls and hard lids only rough in ok
|
Issue PAID IN FULL permit | | | 7/17/2019 | | DONE |
|
|
|