First Notice | 12/18/2019 | 12/18/2019 | 5/15/2020 | | DONE |
Eric Story
|
|
|
This permit finaled on the web by Deb Gooden
|
Final | 12/16/2019 | 12/18/2019 | 12/18/2019 | P | PASS |
Eric Story
|
|
|
Contact: Mike Mulvahill Phone #: ###-#### Inspection requested via web by Deb Gooden Meyers cabinet final ok
|
Final | 9/9/2019 | 9/9/2019 | 9/9/2019 | P | CANC |
Eric Story
|
|
|
Contact: Mike Mulvahill Phone #: ###-#### Inspection requested via web by Deb Gooden No final until meter is installed
|
Permanent Service | 8/14/2019 | 8/14/2019 | 8/14/2019 | P | PASS |
Eric Story
|
|
|
Contact: Mike Mulvahill Phone #: ###-#### Inspection requested via web by Deb Gooden AFC 9181 p/s u/g n ok
|
Permanent Service | 7/30/2019 | 7/31/2019 | 7/31/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Contact: Mike Mulvahill.... street light service inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden 110.24- Available fault current shall be posted prior to other than residential permanent service inspection. 10K rated main Ground rods were attempted to drive vertical, then layed down to 45 degrees and bent over at top. Verbal notice
|
Issue PAID IN FULL permit | | | 7/30/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/30/2019 | | DONE |
|
|
|
This permit was created on the web by Deb Gooden
|