Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberELE19-02906
StatusFinaled
Name CAPITOL ELECTRIC
Site Address 390 S CAPITOL BLVD
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Wiring for a new MOD Pizza
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/9/201910/10/201910/10/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Jim Williams Final ok
Final10/9/201910/9/201910/9/2019PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Jim Williams
300.15 All boxes shall be covered. East show window receptacle, and light 15' in not in.
440.6- Over current protection shall not exceed value on name plate. 45 max 50 amp installed.
Electrical Rough-In10/4/201910/4/201910/4/2019PPASS
DetailsEric Story
Ceiling grid Phone #: ###-#### Inspection requested via web by Jim Williams
Suspended ceiling in back area of electrical area ok to cover
Electrical Rough-In9/3/20199/4/20199/4/2019APASS
DetailsRock A. Hudson
Walls only Phone #: ###-#### Inspection requested via web by Jim Williams
Walls and bathroom hardlids and dining area soffits rough in ok cover.
Electrical Rough-In8/13/20198/13/20198/13/2019PPASS
DetailsRock A. Hudson
Underground Phone #: ###-#### Inspection requested via web by Jim Williams
Service has been de-energized and moved out of what will be new bathroom. Grounding electrode conductor exended by irreversable crimp. All gear to be changed.
Under slab rough in ok cover.
Issue PAID IN FULL permit  8/5/2019 DONE
Payment received via Govolutions
Application received  8/5/2019 DONE
This permit was created on the web by Jim Williams