Final | 9/2/2019 | 9/5/2019 | 9/5/2019 | A | PASS |
Mark Moncarr
|
|
|
Install Manager - Brian Prussia: ###-#### Install Crew Lead - Taylor Barton: ###-#### Electrician - Shaun Shafer: ###-#### Phone #: ###-#### Inspection requested via web by BRS Permitting Ok final. Correction made.
|
Final | 8/26/2019 | 8/27/2019 | 8/27/2019 | A | FAIL |
Mark Moncarr
|
|
|
Install Manager - Brian Prussia: ###-#### Install Crew 4 Lead - Taylor Barton: ###-#### Electrician - Shaun Shafer: ###-#### Phone #: ###-#### Inspection requested via web by BRS Permitting Line side connection using #10. Needs to be #6 as per 230.79(D). Minimum disc size 60a. Conductors need to be minimum #6
|
Electrical Rough-In | 8/20/2019 | 8/21/2019 | 8/21/2019 | A | PASS |
Mark Moncarr
|
|
|
Taylor Barton is best contact Phone #: ###-#### Inspection requested via web by BRS Permitting Ok cover. All items UL listed. Panel model matches paperwork
|
Issue PAID IN FULL permit | | | 8/9/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/9/2019 | | DONE |
|
|
|
This permit was created on the web by BRS Permitting
|