Final | 10/24/2019 | 10/25/2019 | 10/25/2019 | A | PASS |
Rock A. Hudson
|
|
|
Garage code: 4141 -Furnace flex supported. -Service support at 36". -Add receptacle for appliance station in pantry. -GFCI at garage man door in tripped position. Reset and test function at front and back. Phone #: ###-#### Inspection requested via web by Dylan Pierce Final ok
|
Final | 10/23/2019 | 10/24/2019 | 10/24/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Garage code is 4141. Phone #: ###-#### Inspection requested via web by Dylan Pierce 110.3- Front and rear outdoor receptacles not working. Cold. 210.52(C)- Counter top located in pantry shall have receptacle outlets installed so that no point measured along wall line is more than 24" from a receptacle outlet. 348.30- Furnace flex shall be secure with in 12" of termination. 352.30- PVC service riser shall be secured with in 3' of meter base. 440.6- AC ampacity shall not exceed value on nameplate. 25 amp max, 30 amp installed.
|
Rough-In Permanent Service | 8/16/2019 | 8/16/2019 | 8/16/2019 | P | PASS |
Daryl DeGrange
|
|
|
Changes have been made. Phone #: ###-#### Inspection requested via web by Dylan Pierce correction complete, rough-in p/s u/g n ok
|
Rough-In Permanent Service | 8/15/2019 | 8/16/2019 | 8/16/2019 | A | FAIL |
Daryl DeGrange
|
|
|
Please give us a call if you have any question. Thanks, Dylan Phone #: ###-#### Inspection requested via web by Dylan Pierce NEC 210.52(A)(2) 2ft wall space dinning area. NEC 330.23 attic access guard strips. NEC 90.3 expansion coupler at service riser not installed to manufactures specs
|
Issue PAID IN FULL permit | | | 8/15/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/15/2019 | | DONE |
|
|
|
This permit was created on the web by Dylan Pierce
|