Final | 11/19/2019 | 11/20/2019 | 11/20/2019 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas Ok final. Corrections made. Box changed to blue cutin
|
Final | 11/18/2019 | 11/19/2019 | 11/19/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas 314.16- Boxes shall have adequate space for all wiring and devices installed. Kitchen island receptacle serving counter top is a 8 cubic inch box with 11.25 cubic inches of conductor space installed.
|
Rough-In Permanent Service | 9/3/2019 | 9/4/2019 | 9/4/2019 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas Rough-in ok to cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 8/19/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/19/2019 | | DONE |
|
|
|
This permit was created on the web by Heath Thomas
|