Permanent Service | 10/11/2019 | 10/11/2019 | 10/11/2019 | P | PASS |
Rock A. Hudson
|
|
|
Installation is exempt from Title 54 Chapter 10 permitting and inspection requirements. Disconnect does not meet NEC 230.70(A)(1). Utility has exclusive control to energize installation. Include any other code violations 250.50- All Grounding electrodes as described in 250.52(A)(1) thru (A)(7) that are present shall be used as grounding electrode system. #6 bare copper conductor run down pole and coiled at bottom of pole is not described in article listed. p/s o/h n ok
|
Final | 9/30/2019 | 9/30/2019 | 9/30/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Please call 1/2 hour before inspection for electrician to meet you there. Contact Alex Ybarra. Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek With phone call told service is located 18' above grade on pole. 230.70(A)(1)- Service disconnecting means shall be located in a readily accessible location. Max 6'7" to top of handle from grade.
|