Final | 12/3/2019 | 12/4/2019 | 12/4/2019 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Sherry Allen Occ card signed-Final ok
|
Final | 12/2/2019 | 12/3/2019 | 12/3/2019 | A | PART |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Sherry Allen Building checked out fine-Need A/C whip and proper sized OCPD installed in panel
|
Final | 11/27/2019 | 12/2/2019 | 12/2/2019 | A | CANC |
Eric Story
|
|
|
Phone #: ###-#### >> Inspection requested via web by Sherry Allen Inspection cancelled from web by: Sherry Allen
|
Rough-In Permanent Service | 10/18/2019 | 10/21/2019 | 10/21/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Sherry Allen Service only. Available fault current not posted but verified with contractor at 31k available inrush current. Will post by final. p/s u/g n ok
|
Electrical Rough-In | 10/10/2019 | 10/11/2019 | 10/11/2019 | A | PASS |
Eric Story
|
|
|
This is for a cover inspection for the offices in the building. Any questions please call Darin Winters ###-#### Phone #: ###-#### Inspection requested via web by Sherry Allen Offices and bath walls and hard lids ok to cover(fans not installed at this point)
|
Electrical Rough-In | 9/27/2019 | 9/27/2019 | 9/27/2019 | P | PASS |
Eric Story
|
|
|
U/G As per Electrical engineer and building dept have declassified area due to complex BLD and use of building stating use is a storage only and no maintence will be done on planes as it is just "storage" for planes from the weather. No fuel storage in building. U/G in slab ok to cover
|
Electrical Rough-In | 9/24/2019 | 9/25/2019 | 9/25/2019 | A | FAIL |
Eric Story
|
|
|
Please call Bill Ramsey with any questions @ ###-####. We would like an AM inspection for UNDERGROUND COVER INSPECTION. Underground cover is not an option for an inspection type Phone #: ###-#### Inspection requested via web by Sherry Allen 513.8 Underground for Air Craft hanger shall comply with Class 1 Division 1 locations 501.10(A)(1) Type PVC shall be permitted where encased in (2in) thick concrete and provide 24'" deep of conduit
|
Issue PAID IN FULL permit | | | 9/24/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 9/24/2019 | | |
|
|
|
|
Application received | | | 9/24/2019 | | DONE |
|
|
|
This permit was created on the web by Sherry Allen
|
First Notice | 12/4/2019 | 12/4/2019 | | | |
Eric Story
|
|
|
|