Final | 4/15/2020 | 4/15/2020 | 4/15/2020 | P | PASS |
James Ady
|
|
|
Garage code 4267 Phone #: ###-#### Inspection requested via web by Darryn Coburn Corrections made final ok
|
Final | 4/14/2020 | 4/15/2020 | 4/15/2020 | A | FAIL |
James Ady
|
|
|
Garage code 4267, final reinspection Phone #: ###-#### Inspection requested via web by Darryn Coburn 210.52B(2) Small appliance circuits shall serve no others (Patio recep added from Kitchen small appliance circuit)
|
Final | 4/13/2020 | 4/13/2020 | 4/13/2020 | A | FAIL |
James Ady
|
|
|
Garage code 4267, thank you!! Phone #: ###-#### Inspection requested via web by Darryn Coburn 404.4C Switches shall not be installed in tub spaces. (Master tub) 210.52E3 Each balcony shall have 1 recep.(Front)210.11C4 Garage branch circuit shall have no other outlets(Remove mud room from circuit)110.3 Instalation( Garage and W/P circuit reading hot/ground reverse when tripped)
|
Rough-In Permanent Service | 10/30/2019 | 10/31/2019 | 10/31/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s o/h n ok
|
Issue PAID IN FULL permit | | | 10/10/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/10/2019 | | DONE |
|
|
|
This permit was created on the web by Darryn Coburn
|