Final | 11/7/2019 | 11/8/2019 | 11/8/2019 | A | PASS |
James Ady
|
|
|
owner will be there to give access Phone #: ###-#### Inspection requested via web by Charles Davis Final ok
|
Telephone call | | | 10/17/2019 | | DONE |
|
|
|
called DC Elec. value is too low for scope of work. Per Charlie, correct project value is $5,000
|
Rough-In Permanent Service | 10/11/2019 | 10/14/2019 | 10/14/2019 | A | PASS |
Eric Story
|
|
|
all Problems corrected . Phone #: ###-#### Inspection requested via web by Charles Davis Corrections fixed Rough-in ok to cover p/s o/h n ok
|
Rough-In Permanent Service | 10/10/2019 | 10/11/2019 | 10/11/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Thank you :) Phone #: ###-#### Inspection requested via web by Charles Davis 110.3- Family room recessed can junction box cover shall seat tight to box. 210.52(D)- A receptacle outlet shall be installed adjacent to each basin in bathrooms. Master bath has 2 basins. 210.52(E)(3)- Patios or deck accessible form inside house shall have a receptacle outlet installed within its perimeter. Back patio. 300.4- Nail plate above east front garage light. 334.30- Secure NM cable below receptacle in garage near door to house. OK to foam seal.
|
Issue PAID IN FULL permit | | | 10/10/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/10/2019 | | DONE |
|
|
|