Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberELE19-03965
StatusFinaled
Name MUNN JAMES L
Site Address 2690 S ITHACA AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Homeowner Online - Alteration or Repair: Add 2 new outlets to circuit on the shed. One exterior and one interior
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/15/201911/15/201911/15/2019APASS
DetailsTom Saunders
Please call first Phone #: ###-#### Inspection requested via web by James Munn...
disconnect and GFCI protection verified...ok to final
Electrical Rough-In10/28/201910/29/201910/29/2019APASS
DetailsTom Saunders
after 9 am call ahead - James Phone #: ###-####...rough ok to cover...GFCI and toggle switch outside...inside have GFCI and quad outlet
Conference10/17/201910/18/201910/18/2019APASS
DetailsRock A. Hudson
Please call first Phone #: ###-#### Inspection requested via web by James Munn
Existing shed with power from previous installation ELE14-01309 which may have been finaled without looking at shed just hot tub. Shed is missing a required disconnecting means.
Owners scope of work is to junction and add disconnecting at box where power emerges from earth, Feed interior 2 receptacles and add an outdoor receptacle off line side of interior GFCI device to reduce nuisance tripping.
Discussed proteciton of interior wiring, TR and WR receptacles, in use covers, outdoor rating of boxes and cover and sealing outer wall. Pamphlet given, owner has a good under standing of scope of work.
Issue PAID IN FULL permit  10/14/2019 DONE
Payment received via Govolutions
Application received  10/14/2019 DONE
This permit was created on the web by James Munn