First Notice | 12/12/2019 | 12/12/2019 | 7/22/2020 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by Deb Gooden
|
Final | 12/11/2019 | 12/12/2019 | 12/12/2019 | A | PASS |
Rock A. Hudson
|
|
|
CONTACT NAME ROB LAWRENCE Phone #: ###-#### Inspection requested via web by Deb Gooden No card posted. Final ok
|
Final | 12/10/2019 | 12/11/2019 | 12/11/2019 | A | NR |
Rock A. Hudson
|
|
|
Contact: Rob Lawrence Phone #: ###-#### Inspection requested via web by Deb Gooden 2 Receptacles on coffee bar not working, switched power feeding an emergency/ exit. Will recall when ready
|
Electrical Rough-In | 12/5/2019 | 12/5/2019 | 12/5/2019 | P | PASS |
Rock A. Hudson
|
|
|
Contact: Rob Lawrence ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Print stated no fire walls or protection requred. Grid rough in ok cover
|
Electrical Rough-In | 12/4/2019 | 12/5/2019 | 12/5/2019 | A | CANC |
Rock A. Hudson
|
|
|
Contact: Rob Lawrence. ceiling inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden
|
Electrical Rough-In | 10/18/2019 | 10/21/2019 | 10/21/2019 | P | PASS |
Rock A. Hudson
|
|
|
Contact: Rob Lawrence Phone #: ###-#### Inspection requested via web by Deb Gooden Discussed the existing conduits and raceways exposed during remodel that are not up to todays code. If existing are not used as part of this remodel and there are not life safety issuesthey are ok to remain as originally installed. If used in any way they shall conform to today code. BCC 4-05-32- Code violations not to be retained. 110.26- Work clearance shall be provided for HVAC disconnect for electric furnace located in a small enclosed space large enough for unit only and disconnect located above unit with 480 volt circuit present. Coffee bar walls only rough in ok cover
|
Issue PAID IN FULL permit | | | 10/18/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/18/2019 | | DONE |
|
|
|
This permit was created on the web by Deb Gooden
|