Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE19-04035
StatusIssued
Name ROONEY KEELEY ANN
Site Address 2417 W JEFFERSON ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Service has been off for more than a year. No new work is allowed under this permit. This is not the parcel owners main residence.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Service10/28/201910/28/201910/28/2019APASS
DetailsMark Moncarr
1 grd rod added, bonding verified and other corrections made. ps o/h rec ok
Change Status to I  10/28/2019 DONE
should not have been finaled.
Permanent Service10/18/201910/21/201910/21/2019AFAIL
DetailsMark Moncarr
Keeley Phone #: ###-####
1. Grounding electrode system needs updated. Minimum #6 copper, and 2 ground rods atleast 6' apart.
2. Left phase conductor in outside disconnect needs checked. Looks like insulation is split before landing in breaker.
3. Bushing needed in top right portion of inside panel.
Application received  10/18/2019  
Issue PAID IN FULL permit  10/18/2019 DONE