Final | 6/22/2020 | 6/22/2020 | 6/22/2020 | A | PASS |
Tom Saunders
|
|
|
Please call so I can meet you. Thanks Phone #: ###-#### Inspection requested via web by Ron Zimmerman...
new hallway grid...ok to cover job complete...ok to final card signed
|
Electrical Rough-In | 5/6/2020 | 5/6/2020 | 5/6/2020 | P | PASS |
Rock A. Hudson
|
|
|
for ceilings upstairs except one room. Please call when your on your way as I am about 15 minutes away. Thanks Phone #: ###-#### Inspection requested via web by Ron Zimmerman Level 2 misc rooms except "Scada" rm grid rough in ok cover
|
Electrical Rough-In | 5/1/2020 | 5/1/2020 | 5/1/2020 | P | PASS |
Tom Saunders
|
|
|
reinspect ceiling on 1st floor. Call me when you arrive to let you in. Thanks, Ron Phone #: ###-#### Inspection requested via web by Ron Zimmerman...1st floor grid complete...ok to cover
|
Electrical Rough-In | 4/26/2020 | 4/27/2020 | 4/27/2020 | A | PASS |
Tom Saunders
|
|
|
Give me a call when you arrive. I will be on site thanks, Ron Phone #: ###-#### Inspection requested via web by Ron Zimmerman... new ceiling grid...several areas ok to cover...areas given on tag...E hallway, men's bath, breakroom, electrical rm office, locker room, front entry...
|
Electrical Rough-In | 4/27/2020 | 4/27/2020 | 4/27/2020 | A | FAIL |
Tom Saunders
|
|
|
Give me a call when you arrive. I will be on site thanks, Ron Phone #: ###-#### Inspection requested via web by Ron Zimmerman...
correction notice given 1) all data cabling, fire alarm wiring, and any low voltage wiring will be support and not laying on grid 2) S/O cord being used as permanent wiring shall be removed...S/O not rated for permanent wiring or used above grid
|
Electrical Rough-In | 10/30/2019 | 10/31/2019 | 10/31/2019 | A | PASS |
Tom Saunders
|
|
|
rough in for new wall on 2nd floor data room Phone #: ###-#### Inspection requested via web by Ron Zimmerman...ok to cover
|
Issue PAID IN FULL permit | | | 10/30/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/30/2019 | | DONE |
|
|
|
This permit was created on the web by Ron Zimmerman
|
First Notice | 6/22/2020 | 6/22/2020 | | | |
Tom Saunders
|
|
|
|