Final | 7/8/2020 | 7/9/2020 | 7/9/2020 | P | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by danny perrine Ok final
|
Permanent Service | 12/13/2019 | 12/16/2019 | 12/16/2019 | A | CANC |
Mark Moncarr
|
|
|
wrong inspection- Tom Phone #: ###-####
|
Rough-In Permanent Service | 11/22/2019 | 11/25/2019 | 11/25/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by danny perrine Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 11/21/2019 | 11/22/2019 | 11/22/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by danny perrine 110.3- Recessed can covers shall be installed tightly to junction boxes. North garage mud room, north spare bed. 250.64(D)(1)- Grounding electrode conductor shall have an external tap and extend to each service disconnect, 250.148- Metal boxes shall be connected to an equipment grounding conductor. 300.4- Nail plates needed in south garage marked with X. 300.15- NM cables shall terminate in a box. Recess can in utility make up missed. 334.12- NM cables shall not be installed where subject to damage. North garage HRs cut corner due to drywall nailer missing.
|
Issue PAID IN FULL permit | | | 11/12/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/12/2019 | | DONE |
|
|
|
This permit was created on the web by danny perrine
|