Final | 1/7/2020 | 1/8/2020 | 1/8/2020 | A | PASS |
Mark Moncarr
|
|
|
Inspection requested via web by Dan Hobdey Ok final. Corrections made.
|
Final | 12/27/2019 | 12/27/2019 | 12/27/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Contact number Ryan ###-#### Inspection requested via web by Dan Hobdey BCC 4 05 23- Unlawful to conceal- It shall be unlawful for any person to cover or in any way conceal any electrical wiring, cables, conduits or other equipment until the same has been inspected and approved by an electrical inspector. Floor heat. 210.8- All receptacle outlets located in a bathroom shall have GFCI protection. Above vanity. 406.12- All receptacle outlets located in a bathroom shall be tamper resistant type. Above vanity.
|
Electrical Rough-In | 11/13/2019 | 11/14/2019 | 11/14/2019 | A | PASS |
Mark Moncarr
|
|
|
walk around right side of residence for access door Phone #: ###-#### Inspection requested via web by Dan Hobdey Ok cover bath W side of house.
|
Issue PAID IN FULL permit | | | 11/13/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/13/2019 | | DONE |
|
|
|
This permit was created on the web by Dan Hobdey
|