Final | 11/27/2019 | 12/2/2019 | 12/2/2019 | A | PASS |
Tom Saunders
|
|
|
please call Marcus with questions Phone #: ###-#### Inspection requested via web by A.M.E. Office... new service, panel at shop, and required wiring of shop-outlet, interiot light, and exterior egress light complete...ok to final future wiring in shop will require a seperate permit
|
Permanent Service | 11/21/2019 | 11/21/2019 | 11/21/2019 | P | PASS |
Tom Saunders
|
|
|
please call Marcus with Questions Phone #: ###-#### Inspection requested via web by A.M.E. Office... p/s u/g move to new location ok
|
Permanent Service | 11/19/2019 | 11/20/2019 | 11/20/2019 | A | FAIL |
Tom Saunders
|
|
|
call Marcus with questions, Phone #: ###-#### Inspection requested via web by A.M.E. Office... 1) OCPD installed in all-in-one is over manufacturer's rating on bus...110.3(B)
|
Electrical Rough-In | 11/15/2019 | 11/18/2019 | 11/18/2019 | A | PASS |
Daryl DeGrange
|
|
|
This is for an underground inspection. Phone #: ###-#### Inspection requested via web by A.M.E. Office Asked to install warning tape above service feeder conduit to shop. Trench ok cover
|
Issue PAID IN FULL permit | | | 11/15/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/15/2019 | | DONE |
|
|
|
This permit was created on the web by A.M.E. Office
|