Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberELE19-04557
StatusFinaled
Name BENDER ELECTRIC SERVICES
Site Address 407 N PIERCE ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Addition: Add basement, remodel master replace service
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/27/20202/27/20202/27/2020PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by kendall bender Final ok
Permanent Service2/17/20202/18/20202/18/2020APASS
DetailsDaryl DeGrange
###-#### Phone #: ###-#### Inspection requested via web by kendall bender p/s o/h rec ok
Electrical Rough-In12/3/201912/4/201912/4/2019APASS
DetailsRock A. Hudson
Mike Anderson if there are any questions Phone #: ###-#### Inspection requested via web by kendall bender
Rough in ik cover
Electrical Rough-In12/4/201912/4/201912/4/2019PPASS
DetailsRock A. Hudson
Mike Anderson if there are any questions Phone #: ###-#### Inspection requested via web by kendall bender
Grounding electrode system rough in ok cover rest rough in ok cover
Electrical Rough-In12/3/201912/3/201912/3/2019PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by kendall bender
210.52(A)- No point measured along floor line shall be more than 6' from a receptacle outlet. Up bed 14' between receptacles,
250.32- Grounding electrodes shall be terminated at detached building disconnecting means not sub-panel. #4 bare.
300.4- Nail plates needed up storage by switch and down bed in closet.
334.30- NM shall be secured at intervals not to exceed 4 1/2'. At least 3 locations.
Issue PAID IN FULL permit  11/25/2019 DONE
Payment received via Govolutions
Application received  11/25/2019 DONE
This permit was created on the web by kendall bender