Temporary Service | 11/27/2019 | 11/29/2019 | 11/29/2019 | A | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Louis Keller Needed partial final
|
Final | 11/29/2019 | 11/29/2019 | 11/29/2019 | P | PART |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Louis Keller Two 3-pole 60 amp circuits added for additional fryers with receptacles. As per 210.8(B) all receptacle outlets measuring 150 volts or less to ground, 100 amps or less installed in a commercial kitchen shall have GFCI protection. At time of inspection GFCI protection for personel not in place on these new circuits. For TCO contractor for ELE19-03585 other permit for this remodel has provided lock outs for these circuits. As per Daryl DeGrange Chief Electrical inspector this is acceptable for TCO. TCO ok
|
Issue PAID IN FULL permit | | | 11/27/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/27/2019 | | DONE |
|
|
|
This permit was created on the web by Louis Keller
|