Final | 4/30/2020 | 5/1/2020 | 5/1/2020 | P | PASS |
James Ady
|
|
|
garage code 4224 Phone #: ###-#### Inspection requested via web by Troy Ballard Corrections made final ok
|
Final | 4/29/2020 | 4/30/2020 | 4/30/2020 | P | FAIL |
James Ady
|
|
|
garage code 4224 Phone #: ###-#### Inspection requested via web by Troy Ballard Master floor heat GFCI will not reset. re-call
|
Electrical Rough-In | 3/23/2020 | 3/23/2020 | 3/23/2020 | P | PASS |
Rock A. Hudson
|
|
|
Garage code 4224. Master bath floor heat Phone #: ###-#### Inspection requested via web by Troy Ballard Rough in ok cover
|
Rough-In Permanent Service | 3/20/2020 | 3/20/2020 | 3/20/2020 | P | FAIL |
James Ady
|
|
|
Garage code 4224. Floor heat inspection in master bath Phone #: ###-#### Inspection requested via web by Troy Ballard 110.3 Splice between cold and hot leads to be burried in thin set, sensor required to be 24in from wall and centered between parallel heating leads
|
Electrical Rough-In | 3/19/2020 | 3/20/2020 | 3/20/2020 | A | CANC |
James Ady
|
|
|
Inspection for Master Bath floor heat Phone #: ###-#### >> Inspection requested via web by Troy Ballard Inspection cancelled from web by: Troy Ballard
|
Permanent Service | 1/13/2020 | 1/13/2020 | 1/13/2020 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard p/s u/g n ok
|
Electrical Rough-In | 1/13/2020 | 1/13/2020 | 1/13/2020 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard Rough in ok
|
Electrical Rough-In | 1/6/2020 | 1/6/2020 | 1/6/2020 | P | PART |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Nail plates needed above 200A disc for SER. Foam seal only ok
|
Rough-In Permanent Service | 1/6/2020 | 1/6/2020 | 1/6/2020 | P | CANC |
James Ady
|
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn Inspection cancelled from web by: Bob Glenn
|
Issue PAID IN FULL permit | | | 12/4/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/4/2019 | | DONE |
|
|
|
This permit was created on the web by Bob Glenn
|