Final | 2/27/2020 | 2/27/2020 | 2/27/2020 | P | PASS |
Tom Saunders
|
|
|
Garage code is 2020 Phone #: ###-#### Inspection requested via web by Dylan Pierce... correction made...ok to final
|
Final | 2/25/2020 | 2/26/2020 | 2/26/2020 | A | FAIL |
Rock A. Hudson
|
|
|
Garage code is 2020 Phone #: ###-#### Inspection requested via web by Dylan Pierce Only car charging disconnect in place without charging equipment at time of inspection. 210.8(A)- All 15 and 20 amp receptacle outlets located in a garage shall have GFCI protection. Garage heater receptacle.
|
Rough-In Permanent Service | 12/10/2019 | 12/10/2019 | 12/10/2019 | P | CANC |
Tom Saunders
|
|
|
Grounding connections have been/ are currently being addressed. Phone #: ###-#### Inspection requested via web by Dylan Pierce... corrections made rough ok to cover p/s u/g n ok
|
Rough-In Permanent Service | 12/9/2019 | 12/10/2019 | 12/10/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Dylan Pierce 110.14(B)- Conductors shall be spliced or joined by listed listed devices identified for the use. Equipment grounds in all boxes shall be joined by approved means
|
Issue PAID IN FULL permit | | | 12/4/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/4/2019 | | DONE |
|
|
|
This permit was created on the web by Dylan Pierce
|