Final | 1/31/2020 | 1/31/2020 | 1/31/2020 | P | PASS |
James Ady
|
|
|
Access through alley is the best look for blue tarp, Phone #: ###-#### Inspection requested via web by steve sellers corrections made final ok
|
Final | 1/29/2020 | 1/30/2020 | 1/30/2020 | A | FAIL |
Rock A. Hudson
|
|
|
access through alley to garage sliding door to garage should be open Phone #: ###-#### Inspection requested via web by steve sellers 310.16- Minimum size conductor for 60 amp overcurrent device is #6 copper conductor, #8 installed from house to garage.
|
Electrical Rough-In | 12/6/2019 | 12/6/2019 | 12/6/2019 | P | PASS |
James Ady
|
|
|
Access from alley Phone #: ###-#### Inspection requested via web by steve sellers Garage and Storage above. (Access will need provided to strorage area at final) Rough in ok
|
Application received | | | 12/6/2019 | | DONE |
|
|
|
This permit was created on the web by steve sellers
|
Issue PAID IN FULL permit | | | 12/6/2019 | | DONE |
|
|
|
|