Final | 1/2/2020 | 1/2/2020 | 1/2/2020 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ron Zimmerman Final ok
|
Final | 12/30/2019 | 12/31/2019 | 12/31/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ron Zimmerman 210.8(B)- All receptacle outlets located with in 6' of a sink shall have GFCI protection. Breakroom. 300.15- All cables shall terminate in a box. above grid just in from door. 314.25- All boxes shall have covers. Above grid just in from door.
|
Electrical Rough-In | 12/11/2019 | 12/11/2019 | 12/11/2019 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Ron Zimmerman Walls only ok to cover
|
Issue PAID IN FULL permit | | | 12/11/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/11/2019 | | DONE |
|
|
|
This permit was created on the web by Ron Zimmerman
|
First Notice | 1/2/2020 | 1/2/2020 | | | |
Rock A. Hudson
|
|
|
|