Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE19-04815
StatusFinaled
Name ATKINS ELECTRIC LLC
Site Address 1760 W STATE ST
Project Name 
Customer Number1948
ePlanReviewNo
Description
Alteration: Tenant Improvements
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/8/20201/8/20201/8/2020PPASS
DetailsMark Moncarr
Call office or Albert (###-####) if there are any questions. Phone #: ###-#### Inspection requested via web by Bryan Atkins Ok final
Conference1/2/20201/2/20201/2/2020PDONE
DetailsMark Moncarr
Regarding show window outlets
Electrician on-site, Albert ###-#### Phone #: ###-#### Inspection requested via web by Bryan Atkins As per discussion over phone, showroom window recepts will have to be within the 18" zone as per code.
Electrical Rough-In12/23/201912/26/201912/26/2019PPASS
DetailsTom Saunders
Please call Albert when on the way to jobsite. ###-####

Note: Store front window outlets, Cannot lower due to header, customer wants to avoid any surface pipes. Phone #: ###-#### Inspection requested via web by Bryan Atkins...
corrections for grid cover made..ok to cover grid...show outlets shall be approved by inspector for that area...not approved at this time
Electrical Rough-In12/23/201912/24/201912/23/2019ACANC
DetailsMark Moncarr
Ceiling inspection. Note: Store front window outlets, can''t bring down any lower due to header, the customer wants to avoid any surface pipes.

Call Albert ###-#### if you have any questions or issues. Phone #: ###-#### >> Inspection requested via web by Bryan Atkins Inspection cancelled from web by: Bryan Atkins
Electrical Rough-In12/16/201912/17/201912/17/2019APART
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Bryan Atkins
Ceiling not ready
110.12(A)- Unused openings shall be closed by approved means KO seals.
210.62- Show window receptacles shall be located with in 18" of top of windows.
330.30- MC cable shall be secured with in 12" of a box on all power jump between boxes.
Walls only rough in ok cover
Issue PAID IN FULL permit  12/16/2019 DONE
Payment received via Govolutions
Application received  12/16/2019 DONE
This permit was created on the web by Bryan Atkins
First Notice1/8/20201/8/2020   
DetailsMark Moncarr