Final | 6/3/2020 | 6/3/2020 | 6/3/2020 | P | PASS |
James Ady
|
|
|
door open or key by gate fence post under rock Phone #: ###-#### Inspection requested via web by dennis mcneely Final ok
|
Electrical Rough-In | 2/3/2020 | 2/3/2020 | 2/3/2020 | P | PEND |
James Ady
|
|
|
bracing has been done Phone #: ###-#### Inspection requested via web by dennis mcneely Wire running through holes in trusses have been moved and truss repair has ben done. Electrical rough in ok pending building inspection
|
Permanent Service | 1/29/2020 | 1/29/2020 | 1/29/2020 | P | PASS |
James Ady
|
|
|
corrections have been made Phone #: ###-#### Inspection requested via web by dennis mcneely Service only. p/s u/g n ok
|
Rough-In Permanent Service | 1/29/2020 | 1/29/2020 | 1/29/2020 | P | NR |
James Ady
|
|
|
corrections have been made Phone #: ###-#### Inspection requested via web by dennis mcneely Need trusses repaired as per engineer. Wires will need removed for repair. re-call
|
Rough-In Permanent Service | 1/27/2020 | 1/28/2020 | 1/28/2020 | A | NR |
Daryl DeGrange
|
|
|
wired an ready don''t think anyone will be there so if locked key for side door under wood block by front door post Phone #: ###-#### Inspection requested via web by dennis mcneely Drilled engineered trusses need to be adressed, expansion couplers, NEC 320.23(A) guard strips in attic area with in 6ft. of access holes, NEC312.5(C) NM conductor entering service equipment without an connector
|
Issue PAID IN FULL permit | | | 12/31/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/31/2019 | | DONE |
|
|
|
This permit was created on the web by dennis mcneely
|