Print Statement | | | 7/22/2020 | | DONE |
|
|
|
1st past due
|
Print Statement | | | 5/22/2020 | | DONE |
|
|
|
Email this to Christian to mail out
|
Final | 3/10/2020 | 3/11/2020 | 3/11/2020 | A | PASS |
Tom Saunders
|
|
|
The BK dugout project is ready for inspection after changing out the receptacle requested by Andy. Please call ###-#### with questions. Phone #: ###-#### Inspection requested via web by Joe McLean...corrections made...ok to final
|
Final | 3/9/2020 | 3/9/2020 | 3/9/2020 | P | FAIL |
James Ady
|
|
|
The dugout project at Bishop Kelly is ready for final inspection. Please call Pat on your way to the appointment ###-####. Phone #: ###-#### Inspection requested via web by Joe McLean 406.9 Receps intalled in damp locations shall be type"WR" (USB type recep in home team dug out) 314.25 All boxes shall have covers (Missing 4sq blank lighting pull box home team storage area)
|
Electrical Rough-In | 1/8/2020 | 1/8/2020 | 1/8/2020 | P | PASS |
Tom Saunders
|
|
|
The dugout project has underground that needs to be inspected. Pat Bulson is the foreman onsite for CME, ###-####, should there be any questions. Phone #: ###-#### Inspection requested via web by Joe McLean...ok to cover underground left of center consession/announcing booth
|
Issue PAID IN FULL permit | | | 1/7/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 1/7/2020 | | |
|
|
|
|
Application received | | | 1/7/2020 | | DONE |
|
|
|
This permit was created on the web by Joe McLean
|
First Notice | 3/11/2020 | 3/11/2020 | | | |
Tom Saunders
|
|
|
|