Electrical Rough-In | 7/28/2020 | 7/29/2020 | 7/29/2020 | A | PASS |
Rock A. Hudson
|
|
|
John Busnardo (electrician) needs a t-grid for cover rough-in inspection. Please contact him for details. Thank you Phone #: ###-#### Inspection requested via web by A.M.E. Office Back stage grid rough in ok cover
|
Electrical Rough-In | 7/1/2020 | 7/2/2020 | 7/2/2020 | P | PASS |
Daryl DeGrange
|
|
|
Underground inspection - John is contact Phone #: ###-#### Inspection requested via web by Lori Stout Rough-in ok cover N. E. trench of Band Shell or remaining trench.
|
Electrical Rough-In | 6/29/2020 | 6/30/2020 | 6/30/2020 | A | PASS |
Daryl DeGrange
|
|
|
SECTION OF UNDERGROUND JOHN IS CONTACT Phone #: ###-#### Inspection requested via web by Lori Stout Rough-in ok cover new and existing underground ,Northside Band Shell under walkway ramp.
|
Electrical Rough-In | 6/9/2020 | 6/10/2020 | 6/10/2020 | A | PASS |
Rock A. Hudson
|
|
|
CONTACT IS JOHN Phone #: ###-#### Inspection requested via web by Lori Stout Main level walls rough in ok cover
|
Electrical Rough-In | 4/14/2020 | 4/14/2020 | 4/14/2020 | P | PASS |
Rock A. Hudson
|
|
|
John ###-#### Basement rough in ok cover.
|
Conference | 4/14/2020 | 4/14/2020 | 4/14/2020 | P | PASS |
Rock A. Hudson
|
|
|
Discussed what areas of band shell stage area are damp locations and wet locations. As per 406.9 (A) and (B) for 15 and 20 amp, 125 to 250 volt receptacles, the first 12' from the front of overhang shall be considered a wet location subject to beating rain, remaining area beyond 12' back from the front of overhang shall be considered a damp location. 406.9 (B)(2)(b) shall apply to other ampacities due to a band member would not leave their equipment unattended. Determinations made with Daryl Degrange Chief Electrical Inspector and John with AME Electric on site.
|
Conference | 4/1/2020 | 4/1/2020 | 4/1/2020 | P | PASS |
Rock A. Hudson
|
|
|
John Busnardo (electrician) is the contact. He is needing an on-site meeting to go over electrical devices approved by the electrical engineer prior to installation. Thank you Phone #: ###-#### Inspection requested via web by A.M.E. Office Discussed the rating of receptacle boxes and covers in the Eastern exposed recessed portion of structure. Receptacle boxes and covers spec'ed out do not have a rating included with discription. Explained all outdoor receptacles are required to be rated for damp and wet locations where exposed to weather or spray as per 406.9. Also receptacles existing without proper covers would need covers installed compliant with todays code. As per previous conversation about 600+ amps of disconnecting means on 200 amp rated wires would need a main breaker to protect previously installed conductors in gutter. A 200 amp main breaker exists at service location.
|
Issue PAID IN FULL permit | | | 1/16/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/16/2020 | | DONE |
|
|
|
This permit was created on the web by A.M.E. Office
|