Final | 2/4/2020 | 2/4/2020 | 2/4/2020 | P | PASS |
Mark Moncarr
|
|
|
per your instruction 60a ac has been installed in place of 30a. Phone #: ###-#### Inspection requested via web by Ashley Rasmussen Ok final. Correction made.
|
Final | 1/28/2020 | 1/28/2020 | 1/28/2020 | P | FAIL |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Ashley Rasmussen Line side connection requires a minimum 60a disconnect. It is considered a service disconnecting means. 230.79 (D)
|
Electrical Rough-In | 1/21/2020 | 1/21/2020 | 1/21/2020 | P | PASS |
Mark Moncarr
|
|
|
crew onsite ready at 11:30am Phone #: ###-#### Inspection requested via web by Ashley Rasmussen Ok cover. Items UL listed, panels match paperwork
|
Issue PAID IN FULL permit | | | 1/21/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/21/2020 | | DONE |
|
|
|
This permit was created on the web by Ashley Rasmussen
|