Final | 5/15/2020 | 5/15/2020 | 5/15/2020 | P | PASS |
James Ady
|
|
|
garage code 4224 Phone #: ###-#### Inspection requested via web by Troy Ballard final ok
|
Rough-In Permanent Service | 2/6/2020 | 2/6/2020 | 2/6/2020 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard corrections made rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 2/5/2020 | 2/5/2020 | 2/5/2020 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard 300.4- Nail plates shall be installed to protect NM cable where ran thru bored holes that do not maintain 1 1/4" from framing surface. To photo. 314.25- All boxes shall have covers installed completely covering openings. Check all recessed can junction box covers. 1 missing over stairs, several with gaps to boxes including tall ceiling. 352.48- Fitting securing PVC underground service entrance conduit to meter not glued. 408.7- Unused breaker spaces shall be closed by approved means.
|
Issue PAID IN FULL permit | | | 1/23/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/23/2020 | | DONE |
|
|
|
This permit was created on the web by Troy Ballard
|