Final | 3/11/2020 | 3/11/2020 | 3/11/2020 | P | PASS |
James Ady
|
|
|
Corrections are complete Phone #: ###-#### Inspection requested via web by Kendra Lanham corrections made final ok
|
Final | 3/10/2020 | 3/10/2020 | 3/10/2020 | P | FAIL |
James Ady
|
|
|
House is not occupied and key is on top of the meter base. Phone #: ###-#### Inspection requested via web by Kendra Lanham 210.8A6 Kitchen counter receps shall be GFCI protected. 422.31 Hood and Dishwasher need Disc./lockouts. 408.4 Circuit directory needed for garage panel. 110.3 Dead recep stair way half wall, Down laundry room, Bulbs beeded for Bath vanity and down front bed lights.
|
Electrical Rough-In | 1/27/2020 | 1/28/2020 | 1/28/2020 | A | PASS |
James Ady
|
|
|
Re-inspect rough in Phone #: ###-#### Inspection requested via web by Kendra Lanham Up kitchen and full basement ok to cover
|
Electrical Rough-In | 1/24/2020 | 1/27/2020 | 1/27/2020 | P | NR |
James Ady
|
|
|
Basement framing - electrical rough - in Kitchen upstairs - relocate outlets on wall Phone #: ###-#### Inspection requested via web by Kendra Lanham Recep needs added in Down hall as per 210.52H. Need to add smoke detectors. Basement is open and an open path exists to attic. Basement panel needs stuffed and abandoned wire removed Re-call when finished.
|
Issue PAID IN FULL permit | | | 1/24/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/24/2020 | | DONE |
|
|
|
This permit was created on the web by Kendra Lanham
|