Final | 6/18/2020 | 6/18/2020 | 6/18/2020 | A | PASS |
Daryl DeGrange
|
|
|
home owner will be home Phone #: ###-#### Inspection requested via web by steve sellers final ok
|
Electrical Rough-In | 5/4/2020 | 5/4/2020 | 5/4/2020 | P | PASS |
Rock A. Hudson
|
|
|
under tile floor heat in master bathroom, call for access Phone #: ###-#### Inspection requested via web by steve sellers Floor heat rough in ok cover
|
Permanent Service | 3/23/2020 | 3/23/2020 | 3/23/2020 | P | PASS |
Rock A. Hudson
|
|
|
200 amp overhead service, with two ground rods Phone #: ###-#### Inspection requested via web by steve sellers p/s o/h rec ok
|
Electrical Rough-In | 3/20/2020 | 3/20/2020 | 3/20/2020 | P | PASS |
James Ady
|
|
|
Addition and entrance to is at back of house Phone #: ###-#### Inspection requested via web by steve sellers M. bed, bath, closet and living rm ok to cover
|
Conference | 3/13/2020 | 3/13/2020 | 3/13/2020 | P | DONE |
James Ady
|
|
|
Call to meet on site could possibly discuss per phone call Phone #: ###-#### Inspection requested via web by steve sellers Discussed clearances over roof for service drop. 230.24A exception No.2: Where voltage between conductors does not exceed 300V clearance over roof with a 4:11 pitch can be lowered to 3ft.(Idaho power will not allow mast to be raised to allow for higher clearance)
|
Issue PAID IN FULL permit | | | 2/10/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/7/2020 | | DONE |
|
|
|
This permit was created on the web by steve sellers
|