Final | 5/26/2020 | 5/27/2020 | 5/27/2020 | A | PASS |
Rock A. Hudson
|
|
|
Shea *screened* Phone #: ###-#### Final ok
|
Final | 5/20/2020 | 5/21/2020 | 5/21/2020 | P | FAIL |
Rock A. Hudson
|
|
|
Shay *screened* Phone #: ###-#### 210.8(A)- All receptacle outlets installed in garage and outdoor locations shall have GFCI protection. 314.20- All boxes positioned 1/4" or more fron surface of wall shall have spark rings installed. forgot to list on correction but did inform verbally. 314.42- NM cable shall be protected from damage when entering a metal enclosure. Minisplit disconnect. 406.9(A)- Receptacle outlets located in damp or wet locations shall be WR type. Outdoor receptacles not protected from weather shall have in-use covers installed, west side and deck. 406.12(1)- All receptacle outlets required by 210.52 shall be tamper resistant type.
|
Conference | 3/3/2020 | 3/6/2020 | 3/6/2020 | A | PASS |
James Ady
|
|
|
Shea Phone #: ###-#### Discussed verious make up items and when next inspection should be scheduled.
|
Electrical Rough-In | 3/6/2020 | 3/6/2020 | 3/6/2020 | A | PASS |
James Ady
|
|
|
Shea Phone #: ###-#### ADU And garage rough in ok
|
Conference | 2/20/2020 | 2/21/2020 | 2/21/2020 | A | PASS |
James Ady
|
|
|
shea Phone #: ###-#### Discussed alot of info. Required circuits for dwelling unit, wire size AFCI protection, GFCI protection, wall spacing, counter spacing. owner has hand out
|
Issue PAID IN FULL permit | | | 2/19/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/19/2020 | | DONE |
|
|
|
This permit was created on the web by Shea Telford
|