Final | 6/17/2020 | 6/18/2020 | 6/18/2020 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Final ok
|
Final | 6/16/2020 | 6/17/2020 | 6/17/2020 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot 110.3- Lower patio outdoor receptacle shows open ground. 210.8(A)- All 15 and 20 amp receptacle outlets located with in 6' of a sink shall have GFCI protection. 210.51(A)- All wall space 2' or wider shall have a receptacle outlet installed. down bed by door. 210.70- Required luminaired for rooms and outdoors near mandoors shall operate. Programming. 410.10- Securely mounted wall lights with in 3' of master bath tub shall be damp location rated.
|
Electrical Rough-In | 4/21/2020 | 4/22/2020 | 4/22/2020 | P | PASS |
Mark Moncarr
|
|
|
floor heat master bath Phone #: ###-#### Inspection requested via web by Barbara Szurgot Ok cover floor heat mstr.
|
Electrical Rough-In | 3/8/2020 | 3/9/2020 | 3/9/2020 | A | PASS |
Mark Moncarr
|
|
|
rough in Phone #: ###-#### Inspection requested via web by Barbara Szurgot Ok cover whole house.
|
Telephone call | | | 2/24/2020 | | DONE |
|
|
|
Surgot Electric, Called to add radiant floor heating to the permit.
|
Issue PAID IN FULL permit | | | 2/20/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/20/2020 | | DONE |
|
|
|
This permit was created on the web by Barbara Szurgot
|