Temporary Service | 4/6/2020 | 4/7/2020 | 4/7/2020 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard... t/s u/g new ok
|
Temporary Service | 3/23/2020 | 3/24/2020 | 3/24/2020 | A | CANC |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Troy Ballard Inspection cancelled from web by: Troy Ballard
|
Temporary Service | 3/20/2020 | 3/20/2020 | 3/20/2020 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard 110.12- Electrical equipment shall not be damaged. Rust has complromized lugs and meter base jaws. 250.24(A)(4)- A main bonding jumper shall be installed connecting grounded conductor and the grounding electrode conductor.
|
Issue PAID IN FULL permit | | | 2/21/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/21/2020 | | DONE |
|
|
|
This permit was created on the web by Troy Ballard
|