Final | 3/10/2020 | 3/11/2020 | 3/11/2020 | P | PASS |
Rock A. Hudson
|
|
|
There will be someone there. If you have any questions please feel free to contact Fred ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Final ok
|
Final | 3/5/2020 | 3/6/2020 | 3/6/2020 | P | NR |
Rock A. Hudson
|
|
|
There will be people there. If you have any questions please feel free to contact Fred ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan See rough in
|
Electrical Rough-In | 3/5/2020 | 3/6/2020 | 3/6/2020 | P | FAIL |
Rock A. Hudson
|
|
|
There will be people there. If you have any questions please feel free to contact Fred ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan 110.7- Complete wiring installations shall be free of short circuits. Flash evidence on a roof box connector located just west of north emergency exit. Check for damage. 210.8(B)- Roof top receptacle outlets shall have GFCI protection. Did not trip when tested.
|
Issue PAID IN FULL permit | | | 2/25/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/25/2020 | | DONE |
|
|
|
This permit was created on the web by Clayton Morgan
|
First Notice | 3/11/2020 | 3/11/2020 | | | |
Rock A. Hudson
|
|
|
|