Final | 2/28/2020 | 3/2/2020 | 3/2/2020 | A | NR |
James Ady
|
|
|
It will be open. If you have any questions please feel free to contact Jared ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan See rough in notes
|
Electrical Rough-In | 2/28/2020 | 3/2/2020 | 3/2/2020 | A | FAIL |
James Ady
|
|
|
It will be open. If you have any questions please feel free to contact Jared ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan 110.12A All unused openings shall be closed. (Open breaker space in panel) 110.3 Properly install panel dead front. 422.30 Disc shall be provided for all perminantly installed appliances. (Disc shall be within sight of furnace as per manufacturer instructions)
|
Issue PAID IN FULL permit | | | 2/28/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/28/2020 | | DONE |
|
|
|
This permit was created on the web by Clayton Morgan
|