Permanent Service | 6/18/2020 | 6/19/2020 | 6/19/2020 | A | PASS |
Rock A. Hudson
|
|
|
JUSTIN IS CONTACT Phone #: ###-#### Inspection requested via web by Lori Stout Located facing federal way. Available fault current to be posted by final. p/s u/g n ok
|
Electrical Rough-In | 6/18/2020 | 6/19/2020 | 6/19/2020 | A | PASS |
Rock A. Hudson
|
|
|
Justin is contact Phone #: ###-#### Inspection requested via web by Lori Stout Public works underground and pole bases Rough in ok cover
|
Permanent Service | 6/17/2020 | 6/18/2020 | 6/18/2020 | A | FAIL |
James Ady
|
|
|
Jody is contact Phone #: ###-#### Inspection requested via web by Lori Stout 2 permits required for 2 seperate services. 1 for City lights, 1 for Interior lights and sprinkler clock. Project has been completed without inspections, street lights and pole bases installed. No underground inspection, No pole base inspection. Visable ground rods less than 6 ft apart as per 250.50A3
|
Issue PAID IN FULL permit | | | 3/9/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/9/2020 | | DONE |
|
|
|
This permit was created on the web by Lori Stout
|