Permanent Service | 4/8/2020 | 4/9/2020 | 4/9/2020 | A | PASS |
James Ady
|
|
|
New Electrical Service for Subdivision Irrigation pump station on the corner of S Via Privada Ln and E Via Estancia Ln Phone #: ###-#### Inspection requested via web by Kotton Corder 358.42 Couplings and connectors used with EMT shall be made up tight. Could loosen raintight fittings with fingers. Tighten all fittings. Corrections shall be made prior to final. Fault current under 3500A Shall be posted at final p/s u/g n ok
|
Issue PAID IN FULL permit | | | 4/8/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/8/2020 | | DONE |
|
|
|
This permit was created on the web by Kotton Corder
|