Permanent Service | 5/7/2020 | 5/7/2020 | 5/7/2020 | P | PASS |
Eric Story
|
|
|
p/s o/h n ok
|
Final | 5/6/2020 | 5/7/2020 | 5/7/2020 | A | FAIL |
Eric Story
|
|
|
Commercial permanent service Phone #: ###-#### Inspection requested via web by Kevin Koomler 210.8 Multi wire branch circuits shall have a common trip handle
|
Final | 5/6/2020 | 5/6/2020 | 5/6/2020 | P | FAIL |
Tom Saunders
|
|
|
Final inspection Phone #: ###-#### Inspection requested via web by Kevin Koomler..
1) needs to be scheduled as permanent service 2) fees need to reflect a commercial permanent service 3) AFC labelling required for commercial service before power can be given 4) 240V 50A recepticle required to be GFCI protected
|
Telephone call | | | 5/6/2020 | | DONE |
|
|
|
Peggy with Four Star Electric INC called to correct the permit. It was pulled as a temp service and should just be permanent service based off the value.
|
Issue PAID IN FULL permit | | | 5/1/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/1/2020 | | DONE |
|
|
|
This permit was created on the web by Kevin Koomler
|