Temporary Service | 5/4/2020 | 5/5/2020 | 5/5/2020 | P | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Bonnie Page t/s o/h n ok
|
Temporary Service | 5/1/2020 | 5/4/2020 | 5/4/2020 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested vias web by Bonnie Page * Alternative method used- #6 copper installed, Required to be #4 minimum. * Signage required stating altermative method used. Contact stated would drive a ground rod t correct.
|
Issue PAID IN FULL permit | | | 5/1/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/1/2020 | | DONE |
|
|
|
This permit was created on the web by Bonnie Page
|