Alteration or Repair: Upgrading Electrical panel, and wiring through house
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Electrical Rough-In7/29/20207/29/20207/29/2020PPASS
DetailsJames Ady
3480 code Phone #: ###-#### Inspection requested via web by Dave Brueggemann Contractor adding wire for back w/p by a/c at time of rough in. corrections made rough in ok
Electrical Rough-In7/28/20207/28/20207/28/2020PFAIL
DetailsJames Ady
Door code 3480 Phone #: ###-#### Inspection requested via web by Dave Brueggemann corrections not made
Electrical Rough-In7/24/20207/24/20207/24/2020AFAIL
DetailsJames Ady
Code 3480 Phone #: ###-#### Inspection requested via web by Dave Brueggemann 300.15. All wire shall terminate in a box.( Any abandoned, accessible Rag wire shall be removed or terminated in box) 300.4 Nail plates needed in kitchen back spalsh and under living room window. 210.52 Recep need added L&R of master slider and R of living room slider and Dining room wall. 210.70A2. All exits shall have wall controlled exterior lighting.210.52E3 All decks and patios shall have receps. Range and A/C wire need terminated in panel. Please install panel cover or protective front durring construction. Mech room needs light and recep before final
Permanent Service5/5/20205/5/20205/5/2020PCANC
DetailsJames Ady
Door code 3480 Phone #: ###-#### Inspection requested via web by Dave Brueggemann called in twice
Permanent Service5/5/20205/5/20205/5/2020PPASS
DetailsJames Ady
Door code 3480 Phone #: ###-#### Inspection requested via web by Dave Brueggemann p/s o/h rec ok
Permanent Service5/3/20205/4/20205/4/2020AFAIL
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Dave Brueggemann 250.92A1 & A2. Metal raceways containing Service entrance shall be Bonded, Metal enclosures shall be bonded. 200.6B Nuetral conductor shall be identified. 334.30 NM cable shall be supported within 12in of box
Issue PAID IN FULL permit  5/3/2020 DONE
Payment received via Govolutions
Application received  5/3/2020 DONE