DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/14/20207/15/20207/15/2020APASS
DetailsMark Moncarr
Steve - */North side of detached garage Screened*/ Phone #: ###-#### Ok final. Intersystem in place, no labelng of brkrs needed as there are none.
Permanent Service7/15/20207/15/20207/15/2020APASS
DetailsMark Moncarr
I had homeowner meet with a IDP designer to discuss mast height and guy kit. IDP ok'd mast height and was aware that homeowner modified his guy kit to allow attachment within the 6"-12" of weatherhead. p/s o/h n ok
Permanent Service7/7/20207/8/20207/8/2020PCANC
DetailsMark Moncarr
Steven ###-#### Talked with homeowner about scheduling a conference with an IDP designer about service mast height in alley. From roof to top of weatherhead is about 10ft. I would consider it more of a hazard than anything. Homeowner going to get back with me.
Rough-In Permanent Service7/1/20207/7/20207/7/2020PCANC
DetailsMark Moncarr
Inspection of a new combination SE/8ckt panel on North side of garage with 2" RMC up to weatherhead. Two 8'' copper-clad ground rods were also installed on North side of garage approx 8'' apart and connected to ground lug with a continuous 6AWG solid copper wire. Phone #: ###-#### Inspection requested via web by Steve Krag Talked to homeowner, says he's busy at work and asked to reschedule for 7/8/20
Conference6/24/20206/25/20206/25/2020PDONE
DetailsMark Moncarr
Hi, I have recently been in contact with a designer at Idaho Power about my current plan and they are in agreement. I was originally thinking of changing from overhead to underground service but I now plan on adding a new service to my garage and possibly feeding it to my house at a later date. Phone #: ###-#### Inspection requested via web by Steve Krag Discussed install of new 200a feed through on detached garage. # of rods required, drop height over alley, guy kit