Permit Information
Permit NumberELE20-01828
StatusIssued
Name HZ ELECTRIC LLC
Site Address 4667 W IRVING ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: WIRING AND ELECTRICAL SERVICE
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Rough-In Permanent Service5/31/20206/1/20206/1/2020APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Hidajet Zahic
Rough in ok cover p/s o/h n ok
Rough-In Permanent Service5/29/20205/29/20205/29/2020PFAIL
DetailsRock A. Hudson
Inspection requested via web by Hidajet Zahic 210.52(I)- Foyers 60 sq ft. and larger shall have a receptacle oultet installed on all wall 3' and wider.
300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface nail plates shall be installed to protect cables from physical damage. Corners drilled at 45 degree angles.
334.23- All NM cables in attic run within 7' of attic access shall be protected from damage by installed guard strips. Guard strips installed but NM cables run on top on guard strip.
334.30- NM cables shall have supports not to exceed 4 1/2'. 14-3 runs entire lengthh of kitchen with 0 support points.
Issue PAID IN FULL permit  5/29/2020 DONE
Payment received via Govolutions
Application received  5/29/2020 DONE
This permit was created on the web by Hidajet Zahic