Electrical Rough-In | 8/11/2020 | 8/11/2020 | 8/11/2020 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Grid rough in ok cover.
|
Electrical Rough-In | 7/20/2020 | 7/20/2020 | 7/20/2020 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Hardlids rough in ok cover
|
Electrical Rough-In | 6/19/2020 | 6/22/2020 | 6/22/2020 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Access has been provided for perimeter soffit boxes. Walls complete rough in ok cover
|
Electrical Rough-In | 6/15/2020 | 6/16/2020 | 6/16/2020 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton City approved set of prints on site. Insulate ceiling and walls as noted on contractor print rough in ok cover
|
Electrical Rough-In | 6/11/2020 | 6/15/2020 | 6/15/2020 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton South 1/2 of TI and insulate same ceiling ok but no city approved set of prints on site. Informedwork space shall be provided for HVAC units in ceiling. Soffits built too close. Perimeter soffit shall provide access to junction boxes installed at core and shell build. Recall when prints on site.
|
Issue PAID IN FULL permit | | | 6/3/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/3/2020 | | DONE |
|
|
|
This permit was created on the web by Kerri Hamilton
|