Electrical Rough-In | 7/22/2020 | 7/23/2020 | 7/23/2020 | A | PASS |
James Ady
|
|
|
Units 448 and 450 only Phone #: ###-#### Inspection requested via web by Ben Grundhauser Units 448 and 450 only ok to cover
|
Electrical Rough-In | 7/13/2020 | 7/13/2020 | 7/13/2020 | P | PASS |
James Ady
|
|
|
Reinspection of Units 444 and 446 only Phone #: ###-#### Inspection requested via web by Ben Grundhauser corrections made rough in ok
|
Electrical Rough-In | 7/5/2020 | 7/7/2020 | 7/7/2020 | A | FAIL |
James Ady
|
|
|
Units 444 and 446 ONLY are ready for rough/remodel inspection Phone #: ###-#### Inspection requested via web by Ben Grundhauser 210.11C2 and C3. 20A laundry circuit shall have no other outlets, 20A Bath circuit shall have no other outlets. ( Seperate washer and Bath circuit, add circuit for Bath vanity.) At final Bed shall be AFCI protected, J-box in closet of 444 and 446 shall be blanked with no device installed as it is part of the kitchen/ dining room circuit.
|
Issue PAID IN FULL permit | | | 6/24/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/24/2020 | | DONE |
|
|
|
This permit was created on the web by Ben Grundhauser
|