Final | 6/30/2020 | 7/1/2020 | 7/1/2020 | A | FAIL |
James Ady
|
|
|
Homeowner requests that you call 30 minutes to 1 hour before arrival. As early as possible works perfect for her as well. Thank you! Phone #: ###-#### Inspection requested via web by Deslie Duskin Wrong contact number given for Owner.! No answer at office number! 440.22 Application and Selection. Manufacturers rating shall be used. Minnimum circuit ampacity 22.5A maximum overcurrent 25A. (10awg wire 25A breaker needed) 356.30 Supporting LFNC Within 12in of Disc and every 3ft.
|
Final | 6/26/2020 | 6/30/2020 | 6/30/2020 | A | NH |
James Ady
|
|
|
Customer is having surgery in Monday and requests that''s you please call before you show up so that you do not surprise her. Thank you! Phone #: ###-#### Inspection requested via web by Deslie Duskin Wrong phone number for this permit. no access
|
Issue PAID IN FULL permit | | | 6/26/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/26/2020 | | DONE |
|
|
|
This permit was created on the web by Deslie Duskin
|